Liquid Analysis Systems사의 L450 series 화학 분석기는 pH, ORP, ISE, 탁도계 및 다양한 센서를 사용하여 많은 수성 화학 종의 온라인 습식 화학 적정법에 따라 분석합니다. L450의 기능은 신뢰성 및 사용 편의성, 최소 운영 비용에 최적화되어 있습니다.

L450 Series Features
• Auto sample retrieval and preparation
• Result range and trend check
• Auto check of titrant, sample, and electrodes
Through its display and keypad, users can view process status and history, and modify analysis intervals and other configuration parameters. This series offers a variety of hardware options for stream selection, sample preparation, and sample/reagent delivery.
Series Options
• Multi-stream and multi-parameter analysis
• Standard precision titrant dose pumps
• Grab sample port
• Auto sample filter back flush
• Ethernet networking and email messaging
• Outputs for recording, alarming, and/or replenishing • Replenishment systems
L450 Cu Analyzer
The online L450 Cu analyzer measures copper in water by means of reliable and sensitive colorimetric analysis. With automatic background correction, sensor drift common with other methods is eliminated. The method comprises pH buffering, Cu reduction, and a digestion period for color development. To achieve dependable process control, each analysis is automatically replicated and/or trend checked prior to posting, alarming, or replenishing. Sample can be drawn from a pressurized sample stream or pumped from a process tank. For sample with particulate, a sample strainer with automatic backflush is offered as an option.
L450Cu has configuration of Base model with standard precision (20 µl) titrant dose pumps, single/waste pump, inlet, 4-20 mA output
Options
DI Digital input for remote enable of analyses or dosing
DO Digital output relay with settable trip point or other control function
PC Supervisory Windows™ PC software license
G1 Auto grab sample with sipper tube inlet
MS Multi-stream sampling
RR/P Replenishment control (Relay or Pneumatic output options)
SB Sample inlet strainer with auto backflush.
SKB/E Spares kit (Basic or Extended version)
Specifications
Method | pH buffering followed by Cu++ reduction with ascorbic acid to Cu+ and bicinchoninate color development |
Ranges |
0 to 5 ppm |
Inaccuracy | 0.25 ppm |
Cycle time | 7 minutes, typical |
Equipment Stability | 5% per year |
Reagent consumption |
0.2 to 1 ml/test, dependant on sample pH and range |
Power required | 100/240 VAC or 24 VDC |
Sample streams | Standard:1 Optional: up to 8 |
Sample conditions | 0 or 5 to 20 psig, less than 50 µm particulate, 50 to 95 °F. |
Sample connection | ¼” NPT or tube |
Waste | ¼” NPT, ½“ tube adapter provided. |
Leak | 3 /8” tube connection |
Enclosure | 22”Hx18”Wx10”D (55x46x26cm), wall mount, NEMA 4X/IP66 |
Display/Touchscreen | 3” x 2.2”, LCD with backlight |
Outputs |
Standard: 4-20 mA process value, maintenance alarm relay. |
Ambient limits | 4 to 40°C. 5 to 95% humidity, non-condensing. |
Specifications are subject to review of sample conditions.